Accuracy
- 0.1 % of Full Scale
- Typicals J, K, T, E: ± 1° C (± 1.8° F)
- Typicals R & S: ± 4° C (± 7.2° F)
Approvals & Certifications
Humidity
- 5 to 95 % - Non-Condensing
Input Impedance
- 10 megaohms Clamped at ± 24 Vdc
Operating Temperature
- 0° to 60° C (32° to 140° F)
Power Requirement
- Steady State 0.34 W (14.3 mA at 24 Vdc)
Sensor, Probe Type
- C Thermocouple: 0° to 2320° C (32° to 4208° F)
- E Thermocouple: -270° to 1010° C (-454° to 1850° F)
- J Thermocouple: -210° to 770° C (-346° to 1418° F)
- K Thermocouple: -270° to 1380° C (-454° to 2516° F)
- R Thermocouple: 0° to 1760° C (32° to 3200° F)
- S Thermocouple: 0° to 1760° C (32° to 3200° F)
- T Thermocouple: -270° to 410° C (-454° to 770° F)
Voltage
- Common Mode Range: ± 12 Vdc, Max.
- Millivolt Range: ± 25- ± 100 mV