HE579ACM302 Power & Energy Monitor
Brand: HornerHE579ACM302 Power & Energy Monitor
Brand: HornerThe SmartBlock ACM302 is a power and energy monitor designed to interface with Rogowski Coil and NOT standard Current Transformers (CTs).
The ACM302 provides a variety of advanced features, including:
- 3-phase power monitoring with three current (Rogowski coils) and voltage inputs (480 V, direct connect or PTs)
- CsCAN CAN network connection provides a fast flexible communication path
- SmartBlock package allows convenient mounting close to the source to be monitored
- On board relay allows load shedding, alarming or other local switching
Specifications
Brand
Accuracy
- < 1 % of Full Scale
Applications
- Power Monitoring
Communication
- SmartStix I/O
Connectors
- 5-Pin CsCan Connector
Current
- Current Input: 412 mV at 1,000 A
Display
- Status LEDs
Electrical Rating
- Measurement Rating: CAT III 600 V, Max.
Humidity
- 5 to 95 % - Non-Condensing
Input
- 40-600 Vac
- PT Input (or Direct): 480 V secondary
Maximum Voltage
- Contact Voltage: 125 Vac, Max.
- Contact Voltage: 30 Vdc, Max.
Operating Temperature
- 0° to 60° C (32° to 140° F)
Output
- 0.5 A at 125 Vac
- 1 A at 30 Vdc
Power
- 10-30 Vdc
Power Requirement
- Inrush Power Requirement: 14 A for 50 µs
- Steady State Power Requirement: 60 mA at 24 Vdc